iCenta is a UK specialist in +GF+ Signet instrumentation.
Simple to install with time-honoured reliable performance, Signet 2536 Rotor X Paddlewheel Flow Sensors are highly repeatable, rugged sensors that offer exceptional value with little or no maintenance.
The Model 2536 has a process-ready open collector signal and has a wide dynamic flow range of 0.1 to 6 m/s. The sensor measures liquid flow rates in full pipes and can be used in low pressure systems. The Signet 2536 sensors are offered in a variety of materials for a wide range of pipe sizes and insertion configurations. The many material choices including PP, PVDF, and Tefzel® make this model highly versatile and chemically compatible to many liquid process solutions. Sensors can be installed in DN 15 to DN 900 pipes using Signet’s comprehensive line of custom fittings. These custom fittings, which include tees, saddles, and weld-on fittings, seat the sensor to the proper insertion depth into the process flow. The sensors are also offered in configurations for wet tap installation requirements.
Features of the Signet 2536 Rotor X Paddlewheel Flow Sensor include:
- Wide dynamic flow rate from 0.1 to 6 m/s
- Open-collector output
- Simple, economical design
- Highly repeatable output
- Installs into pipe sizes DN 15 to DN 900 (0.5 to 36 in.)
- High resolution and noise immunity
- 6m of cable for standard and Wet tap sensors
- Chemically resistant materials
- Easy to replace rotor.
Other Applications:
- Pure water production
- Filtration systems
- Chemical production
- Liquid delivery systems
- Pump protection
- Scrubbers/gas stacks
- Gravity feed lines
- Not suitable for gases
Specs
Contact Us Today To Enquire About Our Products And Services
Product Specification
The Signet 2536 Rotor X Paddlewheel Flow Sensor is a general-purpose paddle wheel flow sensor offered in a variety of materials and with installation fittings for a wide range of pipe sizes and insertion configurations.
Specification Detail of the Signet 2536 Rotor X Paddlewheel Flow Sensor:
Pipe Size
DN15 – DN900
Material Body
PP, PVDF, Tefzel
Flow Range
1.2 l/min -51,951 m3/hr
Linearity
1%
Operating Temp Range
-18 to 85ᵒC
Pressure Range
1.7 – 14 bar
Outputs & Comms
Open collector, sinking 10 mA max.
Insertion / Inline
Insertion / Inline
Fluid Type
Clean water, dirty water, chemicals
Applicable Liquids
Water, wastewater, chemicals
Power
5 to 24 VDC ± 10% regulated.
Approvals
CE, FCC
Connection Type
Screwed (custom)